| The aquatherm-climasystem is connected by “fusion”.
Simply by heating up the joining elements the plastic melts, allowing the connecting of parts with a single material and forming a permanent connection. The grids can be connected in parallel as well as in series.
Due to the wide range of fusiotherm fittings single connection as well as complete commercial sized installations, including manifolds, can be constructed.
Transition connections for the approved aquatherm-SHT sliding sleeve technology complete the system. |
| 2. aquatherm-climasystem is equipped with
male/female connections for fusion in parallel. |
| 3. Push internal connection of the first grid into the
(socket) heating tool and at the same time the exter-
nal connection of the second grid onto the (spigot)
heating tool. |
| 4 After the required warm-up time of 8 sec., remove
the elements from the tools and immediately push to-
gether (welding depth 13 mm). |
| Wall heating and cooling grids with series connection are fused with diffusion-tight connection pipes and fittings, as described on previous page. |